英语翻译9.2° FLOOR – CONFERENCE ROOM 9.1 CALCULATIONS REVIEW The lighting review shows higher lighting levels than the Dragon International design,as indicated in the premises.In this case the values are too higher (three times higher) so it is reasonable to think that there was some dimming percentage or some changes in lamps,due to specific design criteria,not indicated in the available documentation.The medium lighting level on the working surface (Em)

问题描述:

英语翻译
9.2° FLOOR – CONFERENCE ROOM
9.1 CALCULATIONS REVIEW
The lighting review shows higher lighting levels than the Dragon International design,as
indicated in the premises.
In this case the values are too higher (three times higher) so it is reasonable to think that there
was some dimming percentage or some changes in lamps,due to specific design criteria,not
indicated in the available documentation.
The medium lighting level on the working surface (Em) is:1274 Lx in the Telmotor review
and 395 Lx in Dragon International design.
The Telmotor review uses the same lighting fixtures of the Dragon International design,with
the same accessories,same quantities and the same photometric data with the exception of the
fixtures inside the cave of the ceiling for what it was impossible to find the photometric data
for Dialux,the review was done with OSRAM fixtures with same photometric data as
indicated in the data sheet included in the Dragon International design.
In the Dragon International design,in some ERCO fixtures,the luminous flux was manually
modified,indeed the 22463010 model has 50W lamps with 36° reflector.The original
photometric data given by ERCO shows a flux value of 1200 Lm instead of the one inserted
in Dragon International design that is 900 Lm.
As indicated in the premises,this can be for less efficient lamps or for a dimming percentage
manually inserted in the calculation.
The Dragon International design and the Telmotor review consider part of the conference
room.
In the drawings available the central squares on the ceiling are 110cm wide,the 28W lamps
employed are 114,4cm; seems to be a design error that can be correct with a change of lamps
power at 21W with the same lamps model.In this case the lamps dimension is 84,9cm.

9 .2 °地板-会议室
9.1计算综述
灯光照明审查表明较高水平比龙国际设计,
中所表明的处所.
在这种情况下,价值观念也较高( 3倍) ,这样可以合理地认为,
有些调光百分比或一些变化灯,由于具体的设计标准,而不是
表明在现有的文件.
中期照明水平的工作表面群( EM )是:1274年光照在Telmotor审查
和395勒克斯在龙国际设计.
审查的Telmotor使用同样的灯具龙国际设计,
同样的配件,同样的数量和相同的光度数据除
洞穴内的固定装置的上限是什么不可能找到的光度数据
为Dialux ,审查是与欧司朗灯具同光度数据
中所表明的数据包括在龙国际设计.
在龙国际设计,在一些ERCO装置,该光通量是手动
修改,确实22463010模型50瓦灯泡的36 °反射.原来
光度数据所给予ERCO显示通量价值1200流明,而不是一个插入
在龙国际设计,900流明.
如房地,这可能是效率较低的灯或调光的百分比
手动插入计算.
龙的国际设计和Telmotor审查的一部分,审议会议
房间.
在提供图纸的*广场上的最高限额是一百一十厘米宽,28W灯
就业是114,4厘米;似乎是一个设计错误,可以正确的变动灯
功率21W的相同灯模式.在这种情况下,灯层面84,9厘米.